This paper was a study about noise reduction through flow stabilization in duct using experimental method and numerical analysis at the same time. To determine the fan's type three kinds of fans(axial fan, centrifugal fan, and axial fan with centrifugal type blades) was examined to investigate the suitability for in-line duct. As a result, under the equal number of rotation 2000 RPM, performance of an axial fan with centrifugal type blades was the most superior by 55㏈A at 4.3CMM among other fans. After this, analyzed the results of the numerical analysis to find out the optimum design of pitch angle such as 0°, 10°, 15° and 20°. The intensity of turbulence was low when pitch angle was 15° and air volume became peak by 5.08 CMM. It was observed that axis component of velocity increased gradually when pitch angle increased from 0° to 20°, and embodied noise reduction and improvement of air flow rate through flow stabilization.